UPS for Server Room in Kenya: How to Size One, Which Type to Pick and What to Ask For

The right UPS for server room use in Kenya is an online double conversion unit. Size it from your measured load in watts, and give it enough battery time for a clean shutdown. Kenyan power customers had 3.57 outages a month in the year to June 2025, according to EPRA figures reported by The Eastleigh Voice. So a server room without a UPS will go down.

This guide is for IT managers and business owners who keep servers and network gear in a dedicated room. It shows how to size the load and choose a phase. It also covers runtime, cooling and quotes. However, if your equipment sits in one cabinet, our guide to rack mount UPS sizing goes deeper on that case.

Key takeaways

  • Size a server room UPS from measured watts, so the load stays well under the kW rating and you can still add servers.
  • Schneider Electric advises keeping the total nameplate rating below 60% of the UPS VA rating when you have no measured figures.
  • SIEL Greenpoint covers 1 to 10 kVA in rack or tower form. Safepower S and Evo HF also go up to 40 kVA in three phase.
  • ASHRAE recommends server inlet air of 18 to 27 °C, because every 8 °C rise halves UPS battery life.
  • SIEL units are supplied on order and quoted per room, and Encom quotes are excluding VAT.

Prices and specs checked on 15 November 2026.

SIEL Greenpoint online UPS for server room use in rack and tower positions
SIEL Greenpoint, convertible between rack and tower. Image courtesy of SIEL.

What kind of UPS for server room use is best?

An online double conversion UPS is the best choice, because it rebuilds the power for your servers all the time. The mains is converted to DC and then back to clean AC, so there is no switchover gap when stima imeenda. Cheaper line interactive units switch to battery after a power cut. That short gap is what some servers do not like.

Every SIEL model in this guide has the VFI-SS-111 rating under IEC EN 62040-3. In other words, the output does not depend on the mains. For more detail, read our guide to the SIEL UPS ranges in Kenya. The double conversion explainer also shows how the circuit works.

How do you size a UPS for a server room?

Add up the real watts of everything on the UPS, then choose a model with clear headroom. First, list servers, storage, switches, the firewall and the router. Then read the live draw from each server management page, or from a metered power strip at a busy hour. The nameplate is the last resort, because it shows the maximum and not the daily use.

Watts and VA are not the same thing. In fact, for computer equipment, the VA figure is always equal to or larger than the watt figure. So a UPS has two limits, and you cannot pass either. SIEL rates its units at an output power factor of 1, so 3 kVA is also 3 kW. When you only have nameplate figures, keep the total below 60% of the UPS rating.

Also keep the air conditioner off the server UPS. Air conditioners draw large start-up currents, so they belong on the generator or mains circuit.

Worked example: a small server room in Westlands

Take four servers at 400 W each and a storage box at 150 W. Add two switches at 60 W each and a firewall at 40 W. The total is 1,910 W. A Greenpoint 3K carries it at about 64% of its 3 kW rating. However, when you plan to add two servers, the Greenpoint 6K is the safer pick, because the same load then sits near 32%. A lower load also gives longer battery time.

Which SIEL UPS fits which server room?

Match the load to the right series, then confirm the phase. Single phase suits most small rooms, while three phase suits heavier racks.

ModelPhaseOutputFormat
Greenpoint 1K, 2KSingle1 to 2 kVARack or tower, 2U
Greenpoint 3KSingle3 kVARack or tower, 2U
Greenpoint 6KSingle6 kVARack or tower, 2U
Greenpoint 10KSingle10 kVARack or tower, 2U
Safepower S 10KThree10 kVA, up to 4 in parallelTower, 250 x 900 x 868 mm
Safepower Evo HF 10KThree10 kVA, up to 8 in parallelTower, 440 x 840 x 1320 mm

Specifications courtesy of SIEL. The Safepower S and Evo HF ranges also come in 20, 30 and 40 kVA sizes.

How long should a UPS for a server room run?

Plan for a clean shutdown, not for the whole outage. Planned Kenya Power maintenance can last a full working day. However, no UPS battery is meant to carry servers for eight hours, so that job belongs to a generator.

If you have a generator, the UPS only needs to carry the load until the generator starts. The Safepower range has a diesel mode input for this. Greenpoint also accepts 110 to 300 V input, so a sagging generator does not push the servers onto battery. If you have no generator, size the batteries so every server can save its work and power down in order.

Each Greenpoint 6K takes up to four external battery boxes. The Evo HF also offers LiFePO4 batteries as an option. SIEL does not publish one fixed runtime, because it depends on your load and battery bank. So send us your load list and we will size it.

How do you keep a server room UPS cool and safe?

Keep the room at 18 to 27 °C, which ASHRAE recommends for server inlet air, as reported by Upsite. Batteries are even more sensitive, since every 8 °C rise in temperature cuts battery life in half, according to Schneider Electric. For example, a battery that lasts four years at 25 °C lasts about two at 33 °C.

Weight matters too. The Evo HF 10K weighs 263 kg with batteries, so check the floor before you order. Also leave space around the vents. Avoid a store room with no air conditioning, because heat shortens battery life.

Should a server room UPS be redundant?

Yes, when the room serves paying customers or a clinic, school or bank branch. Besides, Uptime Institute reports that power remains the leading cause of impactful outages. Andy Lawrence of Uptime Intelligence says operators face a growing number of external risks beyond their control, including power grid constraints.

Safepower S units run up to four in parallel and the Evo HF up to eight. So you can add capacity or a standby unit later. Larger rooms should also read our data centre UPS guide and our three phase UPS buying guide.

How do you get a UPS for server room use quoted in Kenya?

Send us your equipment list, your supply type and the runtime you need. Then we will quote a SIEL unit for the room. Encom Digital is the only SIEL retailer in Kenya and East Africa, and units are supplied on order, so there is no list price. To start, use Request a Quote, or Email us. You can also message us on WhatsApp, and browse the full critical and industrial UPS range.

Frequently asked questions

Prices and buying

How much does a UPS for a server room cost in Kenya?

It depends on the size, phase and battery time, so SIEL units are quoted per project. Encom quotes are excluding VAT, and we need your load list because it sets the price.

Where can I buy a SIEL UPS in Kenya?

Encom Digital is the only SIEL retailer in Kenya and East Africa. So send your quote request to us by email or WhatsApp.

Can I buy a UPS for a server room online?

Yes, you can request a quote online. Because every room differs, we confirm the load and battery time before you pay.

Do you supply batteries and installation?

Tell us what you need when you ask for a quote. Then we confirm the battery bank and the installation steps for your site.

Sizing and specs

What size UPS do I need for a server room?

Add up the real watts of all equipment, then add about 30% for growth. For example, a room drawing 1,900 W suits a 3 kVA to 6 kVA online UPS.

What is the best UPS for a server?

An online double conversion UPS is best, because it gives your servers clean power with no switchover gap.

Is single phase or three phase better?

Single phase suits small rooms up to about 10 kVA. However, three phase suits larger rooms, especially when the building already has a three phase supply.

Can I plug an air conditioner into the server UPS?

No, because air conditioners draw large start-up currents. So keep them on the mains or generator circuit.

Using it in Kenya

How long will a UPS run my servers?

It depends on the load and the battery bank. So plan for a clean shutdown, and use a generator for long outages.

Does a UPS work with a generator?

Yes. Greenpoint accepts 110 to 300 V input, while the Safepower range has a diesel mode input.

What temperature should a server room be?

ASHRAE recommends 18 to 27 °C at the server inlet. Also, cooler rooms give batteries a longer life.